NIST logo

Publication Citation: Residential Heat Pump Heating Performance with Single Faults Imposed

NIST Authors in Bold

Author(s): Seok H. Yoon; William V. Payne; Piotr A. Domanski;
Title: Residential Heat Pump Heating Performance with Single Faults Imposed
Published: July 11, 2010
Abstract: A heat pump equipped with a thermostatic expansion valve (TXV) was tested in environmental chambers during steady-state no-fault and imposed-fault operation. The studied system was an R410A split residential heat pump with an 8.8 kW nominal cooling capacity, Seasonal Energy Efficiency Ratio (SEER) of 13, and Heating Seasonal Performance Factor (HSPF) of 7.8. The imposed faults were compressor valve leakage, outdoor improper air flow, indoor improper air flow, liquid line restriction, refrigerant undercharge, and refrigerant overcharge. Evaporator fouling, condenser fouling, and refrigerant overcharge caused the greatest performance degradation. We observed substantial commonality between sensitive features in the heating and cooling modes; however, several different features were identified for the heating mode as more sensitive.
Proceedings: International Refrigeration and Air Conditioning Conference at Purdue
Pages: 8 pp.
Location: West Lafayette, IN
Dates: July 12-15, 2010
Keywords: fault detection and diagnosis; heating mode; heat pump; thermostatic expansion valve
Research Areas: Building Energy Conservation, Building Equipment Efficiency
PDF version: PDF Document Click here to retrieve PDF version of paper (255KB)