Name | Methanol_1m_Pool_R1
|
---|---|
Date | |
Description | Methanol pool fire using thin filament and fine gauge tc to measure flame temperature. Water cooled round pool burner with gravity fed methanol fuel to maintain constant level. Diameter 1.00 m. Depth 10 cm. lip 44.5 cm above floor. Peak HRR value is higher than time averaged peak value reported in NIST.TN.2083. |
Specimen | 1 m diameter pool burner
|
Ignition | propane wand
|
Project ID (s) | |
Test Director | Hamins
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
282
|
14
|
kW
|
Time to Peak Heat Release Rate
|
43.95
|
0.17
|
min
|
Total Heat Released, THR
|
753
|
38
|
MJ
|
Natural Gas Burner Total Heat Released, NGTHR
|
-5
|
- | MJ
|
Heat Release Quality Confirmation, HRQC
|
-0.007
|
- | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
Total Fuel Mass Burned, TFM = THR / HOCf
|
37.8
|
2.4
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
O2 Yield = O2 Consumed / TFM
|
1.42
|
0.10
|
kg/kg
|
CO2 Yield = CO2 Generated / TFM
|
1.41
|
0.10
|
kg/kg
|
CO Yield = CO Generated / TFM
|
0.000169
|
0.000088
|
kg/kg
|
Soot Yield = Soot Generated / TFM
|
below detection limit
|
0.0000075
|
kg/kg
|
Baseline Hood Exhaust Flow
|
1.945
|
0.058
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
48.82
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Methanol
|
- | - |
Hood Size
|
3
|
- | m
|
Effective Duct Diameter
|
0.485
|
0.004
|
m
|
Exhaust Flow Correction Factor
|
0.992
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
13.29
|
0.53
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
19.92
|
0.80
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
![]() |
peak
|
43.95
|
Peak HRR
|
![]() |
2
|
44.78
|
stopped gravity fuel feed
|
![]() |
3
|
48.43
|
snuff fire with cover plate
|
![]() |
4
|
48.82
|
Fire Out
|
![]() |
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314