CornerTest2

Table 1. Test Information
Name
CornerTest2
Date
Description

Mockup room corner test of furniture ignition for CLT project with NRCC. Shelf loading with pine crib stick and kitchen table with 6 chairs. 12 ft corner with 8ft ceiling and no soffit. Ignite with 50 kW natural gas burner. Repeat of test 1 with Gas Rack and FTIR

Specimen
room corner mockup
Ignition
natural gas burner
Project ID (s)
Test Director
Hoehler

Timelapse Video with Heat Release Rate Plot

Table 2. Summary of Test Results
Measurement Value Uc Unit
Peak Heat Release Rate, PHRR
2,083
124
kW
Time to Peak Heat Release Rate
24.30
0.17
min
Total Heat Released, THR
1,572
97
MJ
Natural Gas Burner Total Heat Released, NGTHR
32.78
0.47
MJ
Heat Release Quality Confirmation, HRQC
Not measured -
MJ/MJ
Net Specimen Mass (gravimetric), NM = Mi-Mf
Not measured -
kg
Total Fuel Mass Burned, TFM = THR / HOCf
79.0
9.3
kg
Net Effective Heat of Combustion = THR / NM
Not measured -
MJ/kg
O2 Yield = O2 Consumed / TFM
1.52
0.18
kg/kg
CO2 Yield = CO2 Generated / TFM
1.93
0.24
kg/kg
CO Yield = CO Generated / TFM
0.0243
0.0030
kg/kg
Soot Yield = Soot Generated / TFM
Not measured -
kg/kg
Baseline Hood Exhaust Flow
21.50
0.65
kg/s
Test Duration = Time(Fire Out) - Time(Ignition)
43.67
0.03
min

Uc = Combined Expanded Uncertainty with 95% confidence level

Table 3. Summary of Test Input Parameters
Parameter Value Uc Unit
Fuel Type
Cellulose, Plastic
- -
Hood Size
6
-
m
Effective Duct Diameter
1.975
0.005
m
Exhaust Flow Correction Factor
1.000
0.029
-
Net Heat of Combustion (per unit mass O2), Ef
13.10
0.66
MJ/kg
Net Heat of Combustion(per unit mass fuel), HOCf
19.90
2.00
MJ/kg
Initial Specimen Mass, Mi (gravimetric)
Not measured -
kg
Final Specimen Mass, Mf (gravimetric)
Not measured -
kg
Table 4. Summary of Observed Test Events
Event Time (min) Description Video Snapshot Image
1
0.00
Ignition
2
10.28
chair ignition
3
10.47
Gas burner off
4
14.18
FTIR pump on
5
15.50
Table ignition
6
23.67
all chairs ignited
peak
24.30
Peak HRR
7
28.37
table collapse
8
39.05
start water suppression
9
43.67
Fire Out

Table 5. Supplemental Data Plots

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077(link is external)

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314(link is external)

Report Process Script Version
NFRL_Report_8.3.3
Last Updated May 14, 2021