Name | Heptane_2
|
---|---|
Date | |
Description | Heptane pool fire using 30 cm burner, 1.0 cm lip height, HFGauge_1 at R=0.83 m , two aspirated TCs, bottom aspirated near bidirectional probe middle; bi-directional probe; double screen in front of comaprtment closed, heat exchanger controlling pool burner cooling, HF2=2.34m (48 cm above rim); HF3=3.11 m (48 cm above rim); Liquid TCs at -2.0 cm, -3.0 cm, -4.0 cm at R=1; TCs at -0.25 cm, -3.0 at R=10 cm |
Specimen | Round, Water-Cooled, 30 cm Liquid-Fuel Burner
|
Ignition | propane wand
|
Project ID (s) | |
Test Director | Hamins
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
123.3
|
6.3
|
kW
|
Time to Peak Heat Release Rate
|
65.23
|
0.17
|
min
|
Total Heat Released, THR
|
470
|
24
|
MJ
|
Gas Burner Total Heat Released, NGTHR
|
0
|
- | MJ
|
Heat Release Quality Confirmation, HRQC
|
-255.803
|
- | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
Total Fuel Mass Burned, TFM = THR / HOCf
|
10.58
|
0.63
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
O2 Yield = O2 Consumed / TFM
|
3.29
|
0.22
|
kg/kg
|
CO2 Yield = CO2 Generated / TFM
|
3.11
|
0.22
|
kg/kg
|
CO Yield = CO Generated / TFM
|
0.00877
|
0.00061
|
kg/kg
|
Soot Yield = Soot Generated / TFM
|
0.0165
|
0.0026
|
kg/kg
|
Baseline Hood Exhaust Flow
|
2.111
|
0.063
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
75.25
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Heptane
|
- | - |
Hood Size
|
3
|
- | m
|
Effective Duct Diameter
|
0.483
|
0.004
|
m
|
Exhaust Flow Correction Factor
|
1.033
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
12.68
|
0.50
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
44.40
|
1.30
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
![]() |
2
|
29.45
|
adjusting flow from 2 kg/s to 1 kg/s
|
![]() |
peak
|
65.23
|
Peak HRR
|
![]() |
3
|
74.85
|
Suppression
|
![]() |
4
|
75.25
|
Fire Out
|
![]() |
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314