1B-SCh0-0

Table 1. Test Information
Name
1B-SCh0-0
Date
Description

Steel Closet against target wall. Specimen: Steel closet (32.31 kg) high fuel load: wood cribs (4 x 1A) (76.7 kg) 300 mL Heptane

Specimen
Steel Shed Wood Cribs
Ignition
heptane pan
Project ID (s)
Test Director
Maranghides A

Timelapse Video with Heat Release Rate Plot

Table 2. Summary of Test Results
Measurement Value Uc Unit
Peak Heat Release Rate, PHRR
1,404
73
kW
Time to Peak Heat Release Rate
10.02
0.17
min
Total Heat Released, THR
1,170
63
MJ
Natural Gas Burner Total Heat Released, NGTHR
-3
-
MJ
Heat Release Quality Confirmation, HRQC
Not measured -
MJ/MJ
Net Specimen Mass (gravimetric), NM = Mi-Mf
Not measured -
kg
Total Fuel Mass Burned, TFM = THR / HOCf
72.6
4.5
kg
Net Effective Heat of Combustion = THR / NM
Not measured -
MJ/kg
O2 Yield = O2 Consumed / TFM
1.226
0.085
kg/kg
CO2 Yield = CO2 Generated / TFM
1.58
0.11
kg/kg
CO Yield = CO Generated / TFM
0.01006
0.00072
kg/kg
Soot Yield = Soot Generated / TFM
0.00101
0.00018
kg/kg
Baseline Hood Exhaust Flow
23.95
0.72
kg/s
Test Duration = Time(Fire Out) - Time(Ignition)
32.10
0.03
min

Uc = Combined Expanded Uncertainty with 95% confidence level

Table 3. Summary of Test Input Parameters
Parameter Value Uc Unit
Fuel Type
Cellulose
- -
Hood Size
9
-
m
Effective Duct Diameter
1.975
0.005
m
Exhaust Flow Correction Factor
1.055
0.034
-
Net Heat of Combustion (per unit mass O2), Ef
13.10
0.52
MJ/kg
Net Heat of Combustion(per unit mass fuel), HOCf
16.12
0.50
MJ/kg
Initial Specimen Mass, Mi (gravimetric)
76.70
0.02
kg
Final Specimen Mass, Mf (gravimetric)
Not measured -
kg
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Figure 1. Plot of Heat Release Rate data with event markers and error bars shown at peak.
Table 4. Summary of Observed Test Events
Event Time (min) Description Video Snapshot Image
1
0.00
Ignition
Ignition
2
8.63
window pane cracked
window pane cracked
peak
10.02
Peak HRR
Peak HRR
3
30.02
shed suppression
shed suppression
4
32.10
Fire Out
Fire Out

Table 5. Supplemental Data Plots

Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Exhaust Duct Mass Flow Rate.
Plot of Exhaust Duct Mass Flow Rate.

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314

Report Process Script Version
NFRL_Report_8.4.6
Last Updated September 22, 2022