Name | Test11_PVC_R1
|
---|---|
Date | |
Description | 1/4" thick, 24" wide, 96"tall (in two sections, each 24"x48") panels of PVC mounted to 1" thick Marinite board. Ignite using rectangular propane burner @ 60kW for ignition, burner shut off twice then left on throughout remainder of experiment. Heat flux gauges mounted flush with fuel surface |
Specimen | 1/4" thick, 24" wide, 96" tall panels of PVC
|
Ignition | propane burner
|
Project ID (s) | |
Test Director | Leventon
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
163.2
|
8.8
|
kW
|
Time to Peak Heat Release Rate
|
11.95
|
0.17
|
min
|
Total Heat Released, THR
|
61.9
|
9.0
|
MJ
|
Gas Burner Total Heat Released, NGTHR
|
87.1
|
2.6
|
MJ
|
Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
Total Fuel Mass Burned, TFM = THR / HOCf
|
3.66
|
0.55
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
O2 Yield = O2 Consumed / TFM
|
2.98
|
0.46
|
kg/kg
|
CO2 Yield = CO2 Generated / TFM
|
1.45
|
0.22
|
kg/kg
|
CO Yield = CO Generated / TFM
|
0.193
|
0.030
|
kg/kg
|
Soot Yield = Soot Generated / TFM
|
0.209
|
0.041
|
kg/kg
|
Baseline Hood Exhaust Flow
|
17.21
|
0.52
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
35.40
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Polyvinyl chloride (PVC)
|
- | - |
Hood Size
|
6
|
- | m
|
Effective Duct Diameter
|
1.975
|
0.005
|
m
|
Exhaust Flow Correction Factor
|
1.028
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
12.84
|
0.39
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
16.90
|
0.70
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
|
2
|
6.02
|
Burner Off
|
|
3
|
6.40
|
Burner On
|
|
peak
|
11.95
|
Peak HRR
|
|
4
|
35.40
|
Fire Out
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314