Name | Test19_XLPE6_R1
|
---|---|
Date | |
Description | 1" thick, 24" wide, 96"tall panels (in two sections, each 24"x48") of XLPE Foam (6lb/ft3 density) backed by aluminum foil layer held by wire to 1" thick Marinite board. Ignite using rectangular propane burner @ 60kW for ignition, burner shut off and shielded after sustained flaming of panels. No heat flux data |
Specimen | 1" thick, 24" wide, 96" tall panels of XLPE Foam (6lb/ft3 density)
|
Ignition | propane burner
|
Project ID (s) | |
Test Director | Leventon
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
3,500
|
207
|
kW
|
Time to Peak Heat Release Rate
|
1.28
|
0.17
|
min
|
Total Heat Released, THR
|
278
|
17
|
MJ
|
Gas Burner Total Heat Released, NGTHR
|
2.460
|
0.074
|
MJ
|
Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
7.05
|
0.57
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
39.4
|
4.0
|
MJ/kg
|
O2 Yield = O2 Consumed / NM
|
2.89
|
0.25
|
kg/kg
|
CO2 Yield = CO2 Generated / NM
|
2.87
|
0.25
|
kg/kg
|
CO Yield = CO Generated / NM
|
0.0212
|
0.0019
|
kg/kg
|
Soot Yield = Soot Generated / NM
|
0.0318
|
0.0051
|
kg/kg
|
Baseline Hood Exhaust Flow
|
21.07
|
0.63
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
12.30
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Cross-linked polyethylene foam (XLPE)
|
- | - |
Hood Size
|
6
|
- | m
|
Effective Duct Diameter
|
1.975
|
0.005
|
m
|
Exhaust Flow Correction Factor
|
1.028
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.66
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
40.00
|
8.00
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
7.05
|
0.40
|
kg
|
Final Specimen Mass, Mf (gravimetric)
|
below detection limit
|
0.40
|
kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
![]() |
2
|
0.68
|
gas off
|
![]() |
3
|
0.85
|
shield covering burner
|
![]() |
peak
|
1.28
|
Peak HRR
|
![]() |
4
|
12.17
|
supp
|
![]() |
5
|
12.30
|
Fire Out
|
![]() |
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077