Name | Test49_GPO1_R3
|
---|---|
Date | |
Description | 1/4" thick, 24" wide, 96"tall panels of GPO-1 mounted to 1" thick Marinite board. Ignite using rectangular propane burner @ 60kW for ignition, turn burner off after sustained flaming of panels. Heat flux gauges mounted flush with fuel surface |
Specimen | 1/4" thick, 24" wide, 96" tall panels of GPO-1
|
Ignition | propane burner
|
Project ID (s) | |
Test Director | Leventon
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
522
|
32
|
kW
|
Time to Peak Heat Release Rate
|
6.78
|
0.17
|
min
|
Total Heat Released, THR
|
232
|
16
|
MJ
|
Gas Burner Total Heat Released, NGTHR
|
12.84
|
0.39
|
MJ
|
Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
10.95
|
0.28
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
21.2
|
1.6
|
MJ/kg
|
O2 Yield = O2 Consumed / NM
|
1.783
|
0.073
|
kg/kg
|
CO2 Yield = CO2 Generated / NM
|
1.979
|
0.088
|
kg/kg
|
CO Yield = CO Generated / NM
|
0.0492
|
0.0022
|
kg/kg
|
Soot Yield = Soot Generated / NM
|
0.0353
|
0.0046
|
kg/kg
|
Baseline Hood Exhaust Flow
|
17.44
|
0.52
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
19.67
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Polyester resin (GPO-1)
|
- | - |
Hood Size
|
6
|
- | m
|
Effective Duct Diameter
|
1.975
|
0.005
|
m
|
Exhaust Flow Correction Factor
|
1.028
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.66
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
30.00
|
6.00
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
35.04
|
0.20
|
kg
|
Final Specimen Mass, Mf (gravimetric)
|
24.09
|
0.20
|
kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
|
2
|
3.53
|
gas off
|
|
3
|
6.53
|
pull gauge sheilds
|
|
peak
|
6.78
|
Peak HRR
|
|
4
|
9.05
|
pull gauge sheilds
|
|
5
|
19.67
|
Fire Out
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314