Name | Test50_POMGF_R2
|
---|---|
Date | |
Description | 1/4" thick, 24" wide, 96"tall (in two sections, each 24"x48") panels of POM-GF mounted to 1" thick Marinite board. Ignite using rectangular propane burner @ 60kW for ignition, burner shut off and shielded after sustained flaming of panels. Heat flux gauges mounted flush with fuel surface |
Specimen | 1/4" thick, 24" wide, 96" tall panels of POM-GF
|
Ignition | propane burner
|
Project ID (s) | |
Test Director | Leventon
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
540
|
29
|
kW
|
Time to Peak Heat Release Rate
|
11.10
|
0.17
|
min
|
Total Heat Released, THR
|
367
|
24
|
MJ
|
Gas Burner Total Heat Released, NGTHR
|
10.98
|
0.33
|
MJ
|
Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
24.870
|
0.085
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
14.76
|
0.97
|
MJ/kg
|
O2 Yield = O2 Consumed / NM
|
1.009
|
0.032
|
kg/kg
|
CO2 Yield = CO2 Generated / NM
|
1.318
|
0.048
|
kg/kg
|
CO Yield = CO Generated / NM
|
0.00613
|
0.00022
|
kg/kg
|
Soot Yield = Soot Generated / NM
|
below detection limit
|
0.00059
|
kg/kg
|
Baseline Hood Exhaust Flow
|
20.10
|
0.60
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
50.42
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Polyoxymethylene (POM-GF)
|
- | - |
Hood Size
|
6
|
- | m
|
Effective Duct Diameter
|
1.975
|
0.005
|
m
|
Exhaust Flow Correction Factor
|
1.028
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
14.93
|
0.60
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
15.93
|
1.00
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
33.50
|
0.06
|
kg
|
Final Specimen Mass, Mf (gravimetric)
|
8.63
|
0.06
|
kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
|
2
|
3.03
|
gas off
|
|
3
|
3.43
|
burner shield applied
|
|
4
|
5.93
|
lower gauges exposed
|
|
5
|
6.35
|
upper gauges exposed
|
|
peak
|
11.10
|
Peak HRR
|
|
6
|
50.18
|
water suppression
|
|
7
|
50.42
|
Fire Out
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314