Name | Test53_ABS_R3
|
---|---|
Date | |
Description | 1/4" thick, 24" wide, 96"tall panels of ABS mounted to 1" thick Marinite Board. Ignite using propane burner at 65kW, burner shut off and shielded after sustained flaming of panels. 14 heat flux gauges including radiometers on left wall at z=100,180cm |
Specimen | 1/4" thick, 24" wide, 96" tall panels of ABS
|
Ignition | propane wand
|
Project ID (s) | |
Test Director | Leventon
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
3,541
|
181
|
kW
|
Time to Peak Heat Release Rate
|
3.78
|
0.17
|
min
|
Total Heat Released, THR
|
550
|
31
|
MJ
|
Gas Burner Total Heat Released, NGTHR
|
4.56
|
0.14
|
MJ
|
Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
19.23
|
0.28
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
28.6
|
1.7
|
MJ/kg
|
O2 Yield = O2 Consumed / NM
|
2.123
|
0.075
|
kg/kg
|
CO2 Yield = CO2 Generated / NM
|
2.141
|
0.083
|
kg/kg
|
CO Yield = CO Generated / NM
|
0.0545
|
0.0021
|
kg/kg
|
Soot Yield = Soot Generated / NM
|
0.166
|
0.022
|
kg/kg
|
Baseline Hood Exhaust Flow
|
21.10
|
0.63
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
36.98
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Acrylonitrile Butadiene Styrene (ABS)
|
- | - |
Hood Size
|
6
|
- | m
|
Effective Duct Diameter
|
1.975
|
0.005
|
m
|
Exhaust Flow Correction Factor
|
1.028
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.52
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
30.00
|
0.90
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
19.41
|
0.20
|
kg
|
Final Specimen Mass, Mf (gravimetric)
|
below detection limit
|
0.20
|
kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
|
2
|
1.28
|
Fuel Off
|
|
3
|
1.47
|
burner sheilded
|
|
4
|
2.90
|
gauges unsheilded
|
|
peak
|
3.78
|
Peak HRR
|
|
5
|
36.98
|
Fire Out
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314