Name | Test61_POMGF_R3
|
---|---|
Date | |
Description | 3/8" thick, 24" wide, 96"tall (in two sections, each 24"x48") panels of POM-GF mounted to 1" thick Marinite board. Ignite using rectangular propane burner @ 60kW for ignition, turn burner off after sustained flaming of panels. Heat flux gauges mounted flush with fuel surface. Heat Flux gauges mid and upper to be unshielded as fire grows. Narrow bandpass filter used to image blue flame. |
Specimen | 1/4" thick, 24" wide, 96" tall panels of POM-GF
|
Ignition | propane burner
|
Project ID (s) | |
Test Director | Leventon
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
536
|
29
|
kW
|
Time to Peak Heat Release Rate
|
17.07
|
0.17
|
min
|
Total Heat Released, THR
|
452
|
29
|
MJ
|
Gas Burner Total Heat Released, NGTHR
|
10.98
|
0.33
|
MJ
|
Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
31.16
|
0.28
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
14.52
|
0.94
|
MJ/kg
|
O2 Yield = O2 Consumed / NM
|
1.005
|
0.033
|
kg/kg
|
CO2 Yield = CO2 Generated / NM
|
1.303
|
0.048
|
kg/kg
|
CO Yield = CO Generated / NM
|
0.00666
|
0.00025
|
kg/kg
|
Soot Yield = Soot Generated / NM
|
below detection limit
|
0.00049
|
kg/kg
|
Baseline Hood Exhaust Flow
|
16.62
|
0.50
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
81.63
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Polyoxymethylene (POM-GF)
|
- | - |
Hood Size
|
6
|
- | m
|
Effective Duct Diameter
|
1.975
|
0.005
|
m
|
Exhaust Flow Correction Factor
|
1.028
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
14.93
|
0.59
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
15.93
|
0.50
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
39.13
|
0.20
|
kg
|
Final Specimen Mass, Mf (gravimetric)
|
7.97
|
0.20
|
kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
|
2
|
3.07
|
fuel to burner OFF
|
|
3
|
3.42
|
burner shielded
|
|
peak
|
17.07
|
Peak HRR
|
|
4
|
73.12
|
stir embers, still burning under burner shield
|
|
5
|
81.63
|
Fire Out
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314