Name | C0-3
|
---|---|
Date | |
Description | Fire Barrier: None , Cover Fabric: Polypropylene (3kg), Filling Material: Polyethalene (6kg) and Polyester (4 kg) |
Specimen | upholstered chair mockup
|
Ignition | 18 kW propane square burner
|
Project ID (s) | |
Test Director | Zammarano
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
2,517
|
149
|
kW
|
Time to Peak Heat Release Rate
|
3.30
|
0.17
|
min
|
Total Heat Released, THR
|
321
|
20
|
MJ
|
Natural Gas Burner Total Heat Released, NGTHR
|
0
|
- | MJ
|
Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
12.56
|
0.11
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
25.5
|
1.6
|
MJ/kg
|
O2 Yield = O2 Consumed / NM
|
1.903
|
0.063
|
kg/kg
|
CO2 Yield = CO2 Generated / NM
|
2.154
|
0.080
|
kg/kg
|
CO Yield = CO Generated / NM
|
0.02049
|
0.00076
|
kg/kg
|
Soot Yield = Soot Generated / NM
|
Not measured | - | kg/kg
|
Baseline Hood Exhaust Flow
|
21.57
|
0.65
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
19.43
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Polyurethane Foam
|
- | - |
Hood Size
|
6
|
- | m
|
Effective Duct Diameter
|
1.975
|
0.005
|
m
|
Exhaust Flow Correction Factor
|
1.028
|
0.029
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.66
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
20.00
|
4.00
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
13.23
|
0.08
|
kg
|
Final Specimen Mass, Mf (gravimetric)
|
0.68
|
0.08
|
kg
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314