Table 1. Test Information
Name
Methanol_4
Date
Description

Methanol pool fire using 30 cm round burner, 1 cm lip height, gas sample at 10 cm above rim on centerline; sample 10 min

Specimen
Round, Water-Cooled, 30 cm Liquid-Fuel Burner
Ignition
propane wand
Project ID (s)
Test Director
Hamins

Timelapse Video with Heat Release Rate Plot

Table 2. Summary of Test Results
Measurement Value Uc Unit
Peak Heat Release Rate, PHRR
20.3
1.1
kW
Time to Peak Heat Release Rate
58.03
0.17
min
Total Heat Released, THR
74.0
4.0
MJ
Gas Burner Total Heat Released, NGTHR
-6
-
MJ
Heat Release Quality Confirmation, HRQC
Not measured -
MJ/MJ
Net Specimen Mass (gravimetric), NM = Mi-Mf
Not measured -
kg
Total Fuel Mass Burned, TFM = THR / HOCf
3.71
0.23
kg
Net Effective Heat of Combustion = THR / NM
Not measured -
MJ/kg
O2 Yield = O2 Consumed / TFM
1.415
0.099
kg/kg
CO2 Yield = CO2 Generated / TFM
1.41
0.10
kg/kg
CO Yield = CO Generated / TFM
below detection limit
0.00043
kg/kg
Soot Yield = Soot Generated / TFM
below detection limit
0.00079
kg/kg
Baseline Hood Exhaust Flow
0.998
0.030
kg/s
Test Duration = Time(Fire Out) - Time(Ignition)
68.23
0.03
min

Uc = Combined Expanded Uncertainty with 95% confidence level

Table 3. Summary of Test Input Parameters
Parameter Value Uc Unit
Fuel Type
Methanol
- -
Hood Size
3
-
m
Effective Duct Diameter
0.483
0.004
m
Exhaust Flow Correction Factor
1.033
0.029
-
Net Heat of Combustion (per unit mass O2), Ef
13.29
0.53
MJ/kg
Net Heat of Combustion(per unit mass fuel), HOCf
19.94
0.60
MJ/kg
Initial Specimen Mass, Mi (gravimetric)
Not measured -
kg
Final Specimen Mass, Mf (gravimetric)
Not measured -
kg
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Figure 1. Plot of Heat Release Rate data with event markers and error bars shown at peak.
Table 4. Summary of Observed Test Events
Event Time (min) Description Video Snapshot Image
1
0.00
Ignition
Ignition
2
20.62
adj hood flow. from 1.0 to 0.8 kg/s
adj hood flow. from 1.0 to 0.8 kg/s
peak
58.03
Peak HRR
Peak HRR
3
68.17
Suppression
Suppression
4
68.23
Fire Out
Fire Out

Table 5. Supplemental Data Plots

Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Exhaust Duct Mass Flow Rate.
Plot of Exhaust Duct Mass Flow Rate.

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314

Report Process Script Version