Name | Test029_Sofa_S1'+two(I0+C0)_R1
|
---|---|
Date | |
Description | K-Loveseat (Polyurethane Foam) 1" propane flame ignition. 57199.3g. Camera setting: F4.0,1/60,Gain:0. LED 100% power |
Specimen | Sofa (K-Loveseat)
|
Ignition | propane wand
|
Project ID (s) | |
Test Director | Hamins
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
1,984
|
102
|
kW
|
Time to Peak Heat Release Rate
|
6.25
|
0.17
|
min
|
Total Heat Released, THR
|
811
|
45
|
MJ
|
Gas Burner Total Heat Released, NGTHR
|
0
|
- | MJ
|
Heat Release Quality Confirmation, HRQC
|
Not measured | - | MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
52.116
|
0.028
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
15.56
|
0.86
|
MJ/kg
|
O2 Yield = O2 Consumed / NM
|
1.205
|
0.039
|
kg/kg
|
CO2 Yield = CO2 Generated / NM
|
1.491
|
0.054
|
kg/kg
|
CO Yield = CO Generated / NM
|
0.0302
|
0.0011
|
kg/kg
|
Soot Yield = Soot Generated / NM
|
0.0140
|
0.0029
|
kg/kg
|
Baseline Hood Exhaust Flow
|
20.43
|
0.61
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
34.67
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Polyurethane Foam
|
- | - |
Hood Size
|
9
|
- | m
|
Effective Duct Diameter
|
1.975
|
0.005
|
m
|
Exhaust Flow Correction Factor
|
1.055
|
0.034
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
13.10
|
0.52
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
25.00
|
0.80
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
57.64
|
0.02
|
kg
|
Final Specimen Mass, Mf (gravimetric)
|
5.52
|
0.02
|
kg
|
Event | Time (min) | Description | Video Snapshot Image |
---|---|---|---|
1
|
0.00
|
Ignition
|
![]() |
2
|
4.62
|
Pool Fire underneath
|
![]() |
peak
|
6.25
|
Peak HRR
|
![]() |
3
|
32.03
|
Raking coals
|
![]() |
4
|
34.30
|
water suppression
|
![]() |
5
|
34.67
|
Fire Out
|
![]() |
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)