On the Suitability of CF3Br as a Benchmark replacement Fire Suppressants

Published

Author(s)

B A. Williams, J W. Fleming

Abstract

We investigate the rationale for the use of CF,Br as a reference standard for alternative fire suppresants. Stating efficiencies of alternative agents on a relative basis to that of CF,Br is well founded from an engineering standpoint, but less so from a mechanistic standpoint. The behavior of CF,Br is, in several significant respects, atypical of fire suppressants, which act by catalytic scavenging of flame radicals. In particular, saturation effects, dependence of inhibition efficiency on flame temperature, and changes in flame structure are significantly different for CF,Br than for other catalytic substances including iron and alkali metals. For this reason, the use of CF,Br as an archetype for catalytic suppressants must be qualified to account for these differences.
Citation
Special Publication (NIST SP) - 984-4
Report Number
984-4

Citation

Williams, B. and Fleming, J. (2001), On the Suitability of CF3Br as a Benchmark replacement Fire Suppressants, Special Publication (NIST SP), National Institute of Standards and Technology, Gaithersburg, MD, [online], https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=909056 (Accessed December 26, 2024)

Issues

If you have any questions about this publication or are having problems accessing it, please contact reflib@nist.gov.