Skip to main content
U.S. flag

An official website of the United States government

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Secure .gov websites use HTTPS
A lock ( ) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

Vehicle2

Table 1. Test Information
Name
Vehicle2
Date
Description

2007 blue ICE minivan mass = 1854 kg. 9 gallons of gasoline in fuel tank. Single rear bench seat from 2004 van. Primary ignition with 1 liter kerosene soaked rags to ignite the 6 cm bed of pine straw mulch (23.0 kg) under car.

Specimen
Minivan Vehicle
Ignition
kerosene soaked rags
Project ID (s)
Test Director
Hamins

Timelapse Video with Heat Release Rate Plot

Table 2. Summary of Test Results
Measurement Value Uc Unit
Peak Heat Release Rate, PHRR
11,312
672
kW
Time to Peak Heat Release Rate
10.37
0.07
min
Total Heat Released, THR
9,327
582
MJ
Gas Burner Total Heat Released, NGTHR
1
-
MJ
Heat Release Quality Confirmation, HRQC
Not measured -
MJ/MJ
Net Specimen Mass (gravimetric), NM = Mi-Mf
258.8
5.7
kg
Net Effective Heat of Combustion = THR / NM
36.0
2.4
MJ/kg
O2 Yield = O2 Consumed / NM
2.66
0.10
kg/kg
CO2 Yield = CO2 Generated / NM
2.66
0.11
kg/kg
CO Yield = CO Generated / NM
0.0590
0.0025
kg/kg
Soot Yield = Soot Generated / NM
0.0569
0.0073
kg/kg
Baseline Hood Exhaust Flow
74.0
2.2
kg/s
Test Duration = Time(Fire Out) - Time(Ignition)
99.35
0.03
min

Uc = Combined Expanded Uncertainty with 95% confidence level

Table 3. Summary of Test Input Parameters
Parameter Value Uc Unit
Fuel Type
Generic
- -
Hood Size
15
-
m
Effective Duct Diameter
2.424
0.009
m
Exhaust Flow Correction Factor
1.042
0.032
-
Net Heat of Combustion (per unit mass O2), Ef
13.10
0.66
MJ/kg
Net Heat of Combustion(per unit mass fuel), HOCf
25.00
7.50
MJ/kg
Initial Specimen Mass, Mi (gravimetric)
1,877.00
4.00
kg
Final Specimen Mass, Mf (gravimetric)
1,618.19
4.00
kg
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Figure 1. Plot of Heat Release Rate data with event markers and error bars shown at peak.
Table 4. Summary of Observed Test Events
Event Time (min) Description Video Snapshot Image
1
0.00
Ignition
Ignition
peak
10.37
Peak HRR
Peak HRR
2
16.47
airbag burst sounds
airbag burst sounds
3
17.38
loud bang and sparks ejected
loud bang and sparks ejected
4
90.75
start water supression
start water supression
5
95.08
remove burning magnesium with shovel
remove burning magnesium with shovel
6
99.35
Fire Out
Fire Out

Table 5. Supplemental Data Plots

Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Oxygen Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Dioxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Carbon Monoxide Dry Volume Fraction in hood exhaust stream.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Radiant Heat Flux data with event markers. r= radial distance from center of hood, h=height above floor.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Smoke Laser Extinction Coefficient in hood exhaust stream.
Plot of Exhaust Duct Mass Flow Rate.
Plot of Exhaust Duct Mass Flow Rate.

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314

Report Process Script Version
NFRL_Report_8.6.0
Last Updated April 3, 2025