Name | NGQC_15m_75kgs_12MW
|
---|---|
Date | |
Description | Calorimetry confirmation experiment using 2.5 m natural gas tube burner. Composite Floor compartment walls in place , no floor specimen. |
Specimen | tube gas burner
|
Ignition | electric spark
|
Project ID (s) | |
Test Director | Bryant
|
Measurement | Value | Uc | Unit |
---|---|---|---|
Peak Heat Release Rate, PHRR
|
8,243
|
262
|
kW
|
Time to Peak Heat Release Rate
|
18.57
|
0.17
|
min
|
Total Heat Released, THR
|
3,844
|
131
|
MJ
|
Natural Gas Burner Total Heat Released, NGTHR
|
3,929
|
56
|
MJ
|
Heat Release Quality Confirmation, HRQC
|
0.969
|
0.036
|
MJ/MJ
|
Net Specimen Mass (gravimetric), NM = Mi-Mf
|
Not measured | - | kg
|
Total Fuel Mass Burned, TFM = THR / HOCf
|
76.9
|
2.8
|
kg
|
Net Effective Heat of Combustion = THR / NM
|
Not measured | - | MJ/kg
|
O2 Yield = O2 Consumed / TFM
|
3.67
|
0.18
|
kg/kg
|
CO2 Yield = CO2 Generated / TFM
|
2.89
|
0.15
|
kg/kg
|
CO Yield = CO Generated / TFM
|
below detection limit
|
0.00051
|
kg/kg
|
Soot Yield = Soot Generated / TFM
|
Not measured | - | kg/kg
|
Baseline Hood Exhaust Flow
|
78.1
|
2.3
|
kg/s
|
Test Duration = Time(Fire Out) - Time(Ignition)
|
22.18
|
0.03
|
min
|
Uc = Combined Expanded Uncertainty with 95% confidence level
Parameter | Value | Uc | Unit |
---|---|---|---|
Fuel Type
|
Natural Gas
|
- | - |
Hood Size
|
15
|
- | m
|
Effective Duct Diameter
|
2.424
|
0.009
|
m
|
Exhaust Flow Correction Factor
|
1.042
|
0.032
|
- |
Net Heat of Combustion (per unit mass O2), Ef
|
12.54
|
0.04
|
MJ/kg
|
Net Heat of Combustion(per unit mass fuel), HOCf
|
50.00
|
0.60
|
MJ/kg
|
Initial Specimen Mass, Mi (gravimetric)
|
Not measured | - | kg
|
Final Specimen Mass, Mf (gravimetric)
|
Not measured | - | kg
|
Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077
NIST Fire Calorimetry Database (FCD)
https://doi.org/10.18434/mds2-2314