Test3_4box_r1

Test Director: Kevin McGrattan
Calorimeter Operator: Fernandez
Test Date: 12/3/2019
Process Script Version: NFRL_Report63.m
Test Description: 4 Cardboard boxes, 2x2 array, with crinkle paper. ignite with 8 wicks soaked in 10 mL each, centered at base of each face. ignition marked as last wick is lit with torch

Timelaspe Video
CSV-Datafile
Preliminary Report PDF file
Preliminary Report XLSX file
Video Image of Peak Heat Release Rate

TEST RESULT SUMMARY:

Peak Heat Release Rate, PHRR 944 kW
Time to Peak Heat Release Rate 3.3 min
Total Heat Released, THR 479.27 MJ
Total Fuel Consumed = THR/HOCf 29.731 kg
Total CO Generated 1.064 kg
Total CO2 Generated 47.378 kg
Total Soot Generated 0.0165 kg
Baseline Hood Exhaust Flow 20.86 kg/s
Test Duration 0.74 h

TEST INPUT PARAMETERS:

Fuel Type Cellulose -
Hood Size 6 m
Duct Diameter 1.9753 m
Exhaust Flow Correction Factor 1.028 m
Net Heat of Combustion (per unit mass O2) 13.61 MJ/kg
Net Heat of Combustion, HOCf (per unit mass fuel) 16.12 MJ/kg
Initial Mass of Fuel (if available) 32 kg
Final Mass of Fuel (if available) 0.66 kg


The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019

12-3-2019-NFRLHRR-Test3_4box_r1

 