Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures.

Published

Author(s)

Piotr A. Domanski, W V. Payne

Abstract

R22 and R410A split air-conditioning systems were tested and compared as outdoor temperature ranged form 27.8 oC (82.0 oF) to 54.4 oF (130 oF). The R410A system tests were extended t 68.3 oC (155.0 oF) ambient temperature with a customized compressor. Capacity and efficiency of both systems decreased linearly with increasing outdoor temperature, but the R410A system performance degraded more than the R22 system performance. Operation of the R410A system was stable during all tests, including those with the customized compressor extending up to the 68.3 oF (155.0 oF) outdoor temperature and resulting in a supercritical condition at the condenser inlet. No noticeable changes in noise level or operation on the system was noted.
Proceedings Title
International Refrigeration and Air Conditioning Conference. Proceedings
Conference Dates
July 16-19, 2002
Conference Location
West Lafayette, IN

Keywords

high temperature, ambient temperature, tests, air conditioning, uncertainty

Citation

Domanski, P. and Payne, W. (2002), Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures., International Refrigeration and Air Conditioning Conference. Proceedings, West Lafayette, IN, [online], https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=916952 (Accessed July 18, 2024)

Issues

If you have any questions about this publication or are having problems accessing it, please contact reflib@nist.gov.

Created July 16, 2002, Updated February 17, 2017