Experiment Name Plot of Heat Release Rate Ignition Photo Date/Time Sort descending Project Specimen Fuel Type Total Heat Released (MJ) Peak HRR (kW)
Test_09
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Gravel Burner Natural Gas
31.3
50.5
Test_10
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Electrical Cables PVC, Natural Gas
36.5
44.7
Test_11
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Electrical Cables PVC, Natural Gas
60.5
30.7
Test_12
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
417
641
Test_13
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
142.6
275
Test_14
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Polystyrene
194
186
Test_15
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
33.3
72.2
Test_16
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
55.6
105.0
Test_17
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
65.5
138.2
Test_18
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Plastic assortment Plastics, Natural Gas
131.1
95.3
Test_19
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Gravel Burner Natural Gas
123.7
170.9
Test_20
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Electrical Cables PVC, Natural Gas
126.9
127.2
Test_21
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Electrical Cables PVC, Natural Gas
174
96.5
Test_22
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
36.2
70.9
Test_23
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
31.7
69.1
Test_24
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
74.4
188
Test_25
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Plastic assortment Plastics, Natural Gas
258
185
Test_26
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
61.5
127.3
Test_27
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Box Burner Natural Gas
65.3
133.8
Test_28
Plot of Fire Heat Release Rate with event markers. Uncertainty bar shown at peak value.
Ignition
NRC Electrical Cabinet Experiments Plastic assortment Plastics, Natural Gas
155
88.3

Bryant, R. and Bundy, M. The NIST 20 MW Calorimetry Measurement System for Large-Fire Research, Technical Note (NIST TN) 2077, 2019
https://doi.org/10.6028/NIST.TN.2077

NIST Fire Calorimetry Database (FCD)